Table 4-8 Typical cable sizes for size 2 drives
* Values are beyond the mechanical design of the drive. At this power level it may be
prudent to consider busbars.
Notes for IEC 60364:
Notes for US National Electrical Code:
Model
Maximum
input
current
Continuous
output
current
IEC 60364-5-52
Table A52-12
Column 5 derated
by 0.91 for 40°C
XLPE cables (IEC
60364-5-52 table
A52-14) and 0.77 for
cables bunching
(IEC 60364-5-52
table A52-17 item 4)
US National
Electrical Code
90°C cables at 40°C
ambient
75°C cable at 40°C
ambient
AA
Input
size
mm²
Output
size
mm²
Input
cables
Kcmil
Output
cables
Kcmil
MP350A4(R) MP350A5(R) MP350A6(R) 295 350 120 150 350 400
MP420A4(R) 350 420 150 185 400 500
MP470A5(R) MP470A6(R) 395 470 185 240 500 600
MP550A4(R) 450 550 300 2 x 185 2 x 300 2 x 350
MP700A4(R) MP700A5(R) MP700A6(R) 585 700 2 x 150 2 x 150 2 x 500 2 x 600
MP825A4(R) MP825A5(R)
MP825A6(R) 665 825 2 x 185 2 x 240 2 x 600 3 x 350
MP900A4(R) 725 900 2 x 185 2 x 240 3 x 350 3 x 400
MP1200A4(R) MP1200A5(R) MP1200A6(R) 1050 1200 2 x 300 3 x 240 3 x 600 4 x 400
MP1850A4(R) MP1850A5(R) MP1850A6(R) 1450 1850 4 x 240 4 x 300 * *
1. IEC 60364-5-52 table A 52-12 F method column 5 = Single core cable in free air.
2. IEC 60364-5-52 table A52-14 correction factor for ambient air temperature others
than 30°C.
3. IEC 60364-5-52 table A52-17 item 4 correction factor for groups of more than one
circuit or more than one multi-core cable placed on a single layer on a perforated
tray.
1. Table 310.17 allowable ampacities of single-insulated conducted rated 0 through
2000V in free air, based on ambient air temperature of 30 °C (87 °F).
2. Derating factor of 0.88 is applied for 40 °C to the 75 °C cable column. Table 310.17
is based on 30 °C (86 °F) ambient air temperature.
3. NEC 2005 edition table 310.15(B)(2)(a) shows the adjustment factors for more
than three current-carrying conductors in a race way or cable, for 4-6 current-
carrying conductors 0.80 derating factor is applied.