56 Mentor MP Short Form Guide
www.controltechniques.com Issue Number: 5
Table 4-20 Ferraz Shawmut DC protection fusing for USA size 2 drives
4.6.2 Alternative fusing
Cooper Bussmann or Siba fuses are an acceptable alternative (refer to the Mentor MP
User Guide for more details).
Model
USA
Description Catalog No. Reference No. UL recognized
MP350A4R
American round
fuse
A70QS600-4 Y219993
MP350A5R
A100P600-4 A217373
MP350A6R
MP420A4R A70QS800-4 Z213830
MP470A5R
American round
fuses 2 in parallel
A100P1000-4 (x2) Y217371 (x2)
MP470A6R
MP550A4R A70QS450-4 (x2) F214848 (x2)
MP700A4R A70QS600-4 (x2) Y219993 (x2)
MP700A5R
American round
fuse
A100P1200-4 N218397
MP700A6R
MP825A4R
American round
fuses 2 in parallel
A70QS800-4 (x2) Z213830 (x2)
MP825A5R
American round fuse A100P1200-4 N218397
MP825A6R
MP900A4R
American round
fuses 3 in parallel
A70QS600-4 (x3) Y219993 (x3)
MP1200A4R
American round
fuses 3 in parallel
A70QS700-4 (x3) E202772 (x3)
MP1200A5R
A100P700-4 (x3) T223163 (x3)
MP1200A6R
MP1850A4R
American round
fuses 5 in parallel
A70QS600-4 (x5) Y219993 (x5)
MP1850A5R
A100P600-4 (x5) A217373 (x5)
MP1850A6R
The above DC fuse recommendations are not required for UL conformity of the Mentor
MP drive. Any installations required to meet NEC and/or UL508a panel requirements,
must use recognized fuses that meet the requirements of the standard being applied.
The UL columns above indicate whether the recommended fuse is a UL recognized
component and not its conformance to either NEC or UL508a.
The use of the A100P series fuses is limited to applications with L/R time constants of
30 ms or less. DC fusing is only required on four quadrant (R) drives.
NOTE