Example
Note
Engineering Assistant version 6.3 or later requires the use of Microsoft
®
.NET Framework
version 4.0 or later. If .NET version 4.0 is not currently installed, the software will be
automatically installed during the Engineering Assistant installation. Microsoft .NET
version 4.0 requires an additional 200 MB of disk space.
Connecting to a PC
About this task
Figure 2-1 shows how to connect a computer to a Rosemount 3051SMV.
Figure 2-1: Connecting a PC to the Rosemount 3051SMV
Rosemount 3051SMV without optional
process temperature connection
Rosemount 3051SMV with optional process
temperature connection
A
RL ≥ 250Ω
B
A
RL ≥ 250Ω
B
A. Power supply
B. HART modem
Procedure
1. Remove the cover from the field terminals side of the housing.
2. Power the device as outlined in Connect wiring and power up.
3. Connect the HART modem cable to the PC.
4. On the side marked “Field Terminals,” connect the modem mini-grabbers to the
two terminals marked “PWR/COMM.”
5. Launch the Rosemount 3051SMV Engineering Assistant. For more information on
launching Engineering Assistant, see Launching Engineering Assistant.
6. Once the configuration is complete, replace cover and tighten until metal contacts
metal to meet flameproof/explosion-proof requirements. See Cover installation for
more information.
Reference Manual Configuration
00809-0100-4803 October 2018
Emerson.com/Rosemount 11