Commissioning with the FF configuration program Cerabar M, Deltabar M, Deltapilot M
170 Endress+Hauser
Max Notify/
MAX_NOTIFY
Display
Index: 31
Data type: unsigned8
Access: read only
Displays the number of event reports supported by the device that can exist
unconfirmed at the same time. See also this table, Limit Notify/LIM_NOTIFY
parameter description.
Limit Notify/
LIM_NOTIFY
Entry
Index: 32
Data type: unsigned8
Access: wr for Auto,
OOS
Enter the maximum possible number of event reports that can exist unconfirmed at
the same time. This parameter is not evaluated by Deltabar M 5x, Cerabar M 5x and
Deltapilot M 5x.
Confirm Time/
CONFIRM_TIME
Entry
Index: 33
Data type: unsigned32
Access: wr for Auto,
OOS
Enter the confirmation time for the event report. If the device does not receive
confirmation within this time, the event report is sent to the fieldbus host system
again.
Factory setting:
640000
1
/
32
ms
Write Lock/
WRITE_LOCK
Display
Index: 34
Data type: unsigned8
Access: read only
Displays the status of DIP switch 1 on the electronic insert.
You can lock or unlock parameters relevant to the measured value with DIP switch 1. If
operation is locked by means of the Operator code/S_W_LOCK ( ä 204) parameter,
you can only unlock operation again by means of this parameter.
Possibilities:
Locked: Security locking switched on, i.e. the parameters cannot be written to.
Not locked: Security locking switched off. Depending on the block mode in question,
it is possible to write to the parameters (see Tables, "Parameter" column, access).
Factory setting:
Locked (locking switched on)
Update Event/
UPDATE_EVT
Display
Index: 35
Data type: DS-73
Access: read only
The Update Event/UPDATE_EVT parameter is a structured parameter consisting of
five elements.
UNACKNOWLEDGED
This element is set to "Unacknowledged" as soon as a static parameter changes.
UPDATE_STATE
Indicates whether the change was reported.
TIME_STAMP
Displays the date and time when a static parameter was changed.
STATIC_REVISION
The revision counter is increased each time a static parameter is changed.
RELATIVE_INDEX
Displays the altered parameter in the form of the relative index. See also this Table,
"Parameter, Index" column.
Resource Block - standard parameters
Parameter Description