Cerabar PMP21 IO-Link Description of device parameters
Endress+Hauser 57
Selection • 0 = High active
• 1 = Low active
Factory setting 0
SSC1.2 Config. Mode
Navigation Parameter → Signal Switching Channels 1.2 → SSC1.2 Config. Mode
Description Module of switching signal SSC1.2 for pressure
Selection • 0 = Deactivated
• 1 = Single point
• 2 = Window
• 3 = Two-point
Factory setting 0
SSC1.2 Config. Hyst.
Navigation Parameter → Signal Switching Channels 1.2 → SSC1.2 Config. Hyst.
Description Hysteresis of switching signal SSC1.2 for pressure
Selection No selection. The user is free to edit the values.
Switching delay time, output 2 (dS2)
Navigation Parameter → Signal Switching Channels 1.2 → Switching delay time, output 2 (dS2)
Description To prevent switching on and switching off at values around the switch point, you can
configure a delay for the specific points within a range of 0 to 50 s with a resolution of 2
decimal places.
If the measured value leaves the switching range during the configured delay time, the
delay time starts again.
Selection 0.00 to 50.00 s
Factory setting 0 s
Switchback delay time, output 2 (dR2)
Navigation Parameter → Signal Switching Channels 1.2 → Switchback delay time, output 2 (dR2)