Deltabar PMD75B HART Diagnostics and troubleshooting
Endress+Hauser 57
11.1.4 Response of current output to errors
The response of the current output to errors is defined by the following parameters:
Navigation
"Application" submenu → Current output
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Failure mode Defines which current the output assumes in
the case of an error. ‘Min.’: < 3.6mA ‘Max.’:
> 21.95mA ‘Last valid value’: Last valid
value before occurrence of the error. ‘Actual
value’: Output current is equal to the
measured value; error is ignored. ‘Defined
value’: User defined value.
• Min.
• Max.
• Last valid value
• Actual value
Max.
Failure current Enter current output value in alarm
condition.
21.5 to 23 mA 22.5 mA