EasyManua.ls Logo

Endress+Hauser Deltabar PMD75B HART - Current Output and Diagnostic Information; Response of Current Output to Errors

Endress+Hauser Deltabar PMD75B HART
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Deltabar PMD75B HART Diagnostics and troubleshooting
Endress+Hauser 57
11.1.4 Response of current output to errors
The response of the current output to errors is defined by the following parameters:
Navigation
"Application" submenu → Current output
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Failure mode Defines which current the output assumes in
the case of an error. ‘Min.’: < 3.6mA ‘Max.’:
> 21.95mA ‘Last valid value’: Last valid
value before occurrence of the error. ‘Actual
value’: Output current is equal to the
measured value; error is ignored. ‘Defined
value’: User defined value.
Min.
Max.
Last valid value
Actual value
Max.
Failure current Enter current output value in alarm
condition.
21.5 to 23 mA 22.5 mA

Table of Contents

Related product manuals