Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (via local operation and FieldCare)
Endress+Hauser 121
9.5.2 Manual entry of the linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
This is a theoretical calibration, i.e. the points for the linearization table are known.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. For information
on how to perform position adjustment, ä 142, Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
For a description of the parameters mentioned, see
ä 142, Table 6: OPERATING MENU SETTINGS POSITION ADJUSTMENT
ä 146, Table 8: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level easy pressure"
ä 166, Table 12: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
MODE "Pressure linearized"
ä 186, Table 18: GROUP SELECTION OPERATING MENU SETTINGS
LINEARIZATION – Local operation
ä 189, Table 19: MANUFACTURER VIEW OPERATING MENU SETTINGS
LINEARIZATION – FieldCare
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".