3.1 Wiring examples
The following figures show wiring examples for typical applications: In general:
If possible, ground both ends of the signal line screening. If this is not possible,
ground at the sensor side only.
In hazardous areas, the signal line may be grounded at the sensor side only.
Observe the instructions in the certificate.
4...20 mA with HART
Use screened, twisted pairs.
Min. load for HART 250
Max. load:
Housing F12: 1100 , for EEx ia 820
Housing T12: 750 , for EEx e 750 .
Power
(load dependent, see Chapter 9.2.)
Housing F12
standard 16...36 VDC
EEx ia 16...30 VDC
Housing T12
standard 16...30 VDC
EEx e 16...30 VDC
System integration via
4...20 mA with HART
System Integration via interface FXN 672
and Rackbus gateway ZA 67x.
Power: supplied by FXN 672
Screened, twisted pairs are recommended
for the loop-power line.
1234
L- L+
I+ I-
BA171Y24
optional PLC
with active
output
power
plant
ground
DXR 275
or
FXA 191
communication
resistor
test sockets
(via interlock
diode)
Caution!
1
d4
ZA 67x
FXN 672
d2
234
L- L+
I+ I-
BA171Y25
plant
ground
Rackbus
Micropilot FMR 231 Chapter 3 Connection
Endress+Hauser 15