7.9 Simulation
Where appropriate, the simulation function allows the linearisation and analogue output
to be tested. The following possibilities exist:
•
Simulation of level: fields V0H0, V0H9 and V9H8 follow the set values.
•
Simulation of volume: fields V0H0, V0H9 and V9H8 follow the set values.
•
Simulation of current: field V9H8 follows the set values.
Depending upon requirement, enter a value in V9H7: Warning E613 appears in V9H0
during simulation.
# VH Entry Significance
➤ Simulation
Simulation level
1 V9H6 1
H
Simulation level
V9H7 ****
H
Enter level
V9H7 ––––
VH
Current
V0H0 –––– H Level/volume
Simulation volume
2 V9H6 2
H
Simulation volume
V9H7 ****
VH
Enter volume
V9H7 –––– Current
V0H0 –––– VH Volume
Simulation current
3 V9H6 3
H
Simulation
current
V9H7 ****
H
Enter current
V9H8 ––––
VH
Current
V0H0 –––– VH Level/volume
End simulation
4 V9H6 0
H
Simulation off
BA171Y47
V9H7: L (m/ft); V9H8: V (hl/gal...)
V, L
L
V0H6
V0H5
4mA 20mAcurrent
V (hl/gal...)
V0H6
V0H5
V9H7: L m/ft
V9H9
V9H8
Micropilot FMR 231 Chapter 7 Trouble-Shooting
Endress+Hauser 43