EasyManua.ls Logo

Endress+Hauser FMR 231 - 6.4 Analogue output; Settings; Example: Analogue output

Endress+Hauser FMR 231
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4 Analogue output
The analogue output can be set using the fields listed below. If required, a scaling or
inversion of the output can be set in V0H5 and V0H6.
Settings
Example:
Analogue output
# VH Entry Significance
Operating mode
1 V8H1 e.g. 1
H
Output min. 4 mA
0: off
1: on
Basic calibration
2 V0H4 e.g. 10
H
Output damping
3 V0H5 e.g. 40%
H
Value for 4 mA
4 V0H6 e.g. 70%
H
Value for 20 mA
5 V0H7 e.g. 0
VH
Safety alarm
0 = MIN
1 = MAX
2 = HOLD
BA171Y44
100%
0%
V0H6
level
V0H5
4mA 20mA
Field Parameter Significance
V8H1 Current output min 4 mA
0: off
1: on
Sets behaviour of analogue output. Default = 1.
0: 3.8...20.5 mA continuous output
1: as above, but 4 mA limit in normal operation
The ouput follows the setting in V0H7 if a fault is detected
V0H4 Output damping τ
0...255 s
Influences the time it takes for the analogue output to
react to a sudden change in level (63% of steady-state
value). Default 5 s. Increasing the value damps the effect
of e.g. rapid level changes on the measured value.
V0H5
V0H6
4 mA value
20 mA value
Lower range-value of analogue output
Upper range-value of analogue output
Entry in % or after a linearisation in technical units
V0H7 Safety alarm (Output on alarm)
0: MIN
1: MAX
2: HOLD
In order to signal an alarm, the measured value assumes
the selected value.
MIN = 3.8 mA; MAX = 22 mA
HOLD = holds last current value
V9Hß Current output Displays current value of analogue output
Micropilot FMR 231 Chapter 6 Calibration with Display/Remote Operation
Endress+Hauser 31

Related product manuals