Proline Promag P 500 HART Commissioning
Endress+Hauser 111
10.4.9 Configuring the low flow cut off
The Low flow cut off wizard systematically guides the user through all the parameters
that must be set to configure low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
→  111
On value low flow cutoff
→  111
Off value low flow cutoff
→  111
Pressure shock suppression
→  111
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign process variable Select process variable for low
flow cut off.
Off
Volume flow
Mass flow
Corrected volume
flow
Volume flow
On value low flow cutoff One of the following options is
selected in the Assign process
variable parameter
(→  111):
Volume flow
Mass flow
Enter on value for low flow cut
off.
Positive floating-
point number
Depends on country
and nominal
diameter
Off value low flow cutoff One of the following options is
selected in the Assign process
variable parameter
(→  111):
Volume flow
Mass flow
Corrected volume flow
Enter off value for low flow cut
off.
0 to 100.0 % 50 %
Pressure shock suppression One of the following options is
selected in the Assign process
variable parameter
(→  111):
Volume flow
Mass flow
Corrected volume flow
Enter time frame for signal
suppression (= active pressure
shock suppression).
0 to 100 s 0 s