Commissioning Proline Promag P 500 HART
116 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Switch-on delay In the Relay output function
parameter, the Limit option is
selected.
Define delay for the switch-on
of status output.
0.0 to 100.0 s 0.0 s
Failure mode Define output behavior in
alarm condition.
Actual status
Open
Closed
Open
* Visibility depends on order options or device settings
10.4.13 Configuring the double pulse output
The Double pulse output submenu guides the user systematically through all the
parameters that have to be set for configuring the double pulse output.
Navigation
"Setup" menu → Double pulse output
Double pulse output
Master terminal number
→  116
Slave terminal number
→  116
Signal mode
→  116
Assign pulse output 1
→  117
Measuring mode
→  117
Value per pulse
→  117
Pulse width
→  117
Failure mode
→  117
Invert output signal
→  117
Parameter overview with brief description
Parameter Description Selection / User interface / 
User entry
Factory setting
Signal mode Select the signal mode for the double pulse
output.
Passive
Active
Passive NAMUR
Passive
Master terminal number Shows the terminal numbers used by the
master of the double pulse output module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
Slave terminal number Not used
24-25 (I/O 2)
22-23 (I/O 3)