Proline Promag P 500 HART Commissioning
Endress+Hauser 117
Parameter Description Selection / User interface / 
User entry
Factory setting
Assign pulse output 1 Select process variable for pulse output. Off
Volume flow
Mass flow
Corrected volume flow
Off
Measuring mode Select measuring mode for pulse output. Forward flow
Forward/Reverse flow
Reverse flow
Reverse flow compensation
Forward flow
Value per pulse Enter measured value at which a pulse is
output.
Signed floating-point number Depends on country and
nominal diameter
Pulse width Define time width of the output pulse. 0.5 to 2 000 ms 0.5 ms
Failure mode Define output behavior in alarm condition. Actual value
No pulses
No pulses
Invert output signal Invert the output signal. No
Yes
No