Proline Promag P 500 HART Commissioning
Endress+Hauser 117
Parameter Description Selection / User interface /
User entry
Factory setting
Assign pulse output 1 Select process variable for pulse output. • Off
• Volume flow
• Mass flow
• Corrected volume flow
Off
Measuring mode Select measuring mode for pulse output. • Forward flow
• Forward/Reverse flow
• Reverse flow
• Reverse flow compensation
Forward flow
Value per pulse Enter measured value at which a pulse is
output.
Signed floating-point number Depends on country and
nominal diameter
Pulse width Define time width of the output pulse. 0.5 to 2 000 ms 0.5 ms
Failure mode Define output behavior in alarm condition. • Actual value
• No pulses
No pulses
Invert output signal Invert the output signal. • No
• Yes
No