Proline Promag P 500 HART Commissioning
Endress+Hauser 131
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Assign simulation process variable Select a process variable for
the simulation process that is
activated.
Off
Volume flow
Mass flow
Corrected volume
flow
Flow velocity
Conductivity
*
Off
Process variable value Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Status input simulation Switch simulation of the status
input on and off.
Off
On
Off
Input signal level In the Status input simulation
parameter, the On option is
selected.
Select the signal level for the
simulation of the status input.
High
Low
High
Current input 1 to n simulation Switch simulation of the
current input on and off.
Off
On
Off
Value current input 1 to n In the Current input 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
0 to 22.5 mA 0 mA
Current output 1 to n simulation Switch the simulation of the
current output on and off.
Off
On
Off
Value current output 1 to n In the Current output 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA 3.59 mA
Frequency output simulation 1 to n In the Operating mode
parameter, the Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
Off
On
Off
Frequency value 1 to n In the Frequency output
simulation 1 to n parameter,
the On option is selected.
Enter the frequency value for
the simulation.
0.0 to 12 500.0 Hz 0.0 Hz
Pulse output simulation 1 to n In the Operating mode
parameter, the Pulse option is
selected.
Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
(→  104) defines the
pulse width of the pulses
output.
Off
Fixed value
Down-counting
value
Off
Pulse value 1 to n In the Pulse output
simulation 1 to n parameter,
the Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65 535 0
Switch output simulation 1 to n In the Operating mode
parameter, the Switch option
is selected.
Switch the simulation of the
switch output on and off.
Off
On
Off
Switch status 1 to n Select the status of the status
output for the simulation.
Open
Closed
Open
Relay output 1 to n simulation Switch simulation of the relay
output on and off.
Off
On
Off
Switch status 1 to n The On option is selected in
the Switch output simulation
1 to n parameter parameter.
Select status of the relay
output for the simulation.
Open
Closed
Open