Technical data Proline Promag P 500 HART
182 Endress+Hauser
Maximum switching
capacity (passive)
DC 30 V, 0.1 A
AC 30 V, 0.5 A
Assignable functions Off
On
Diagnostic behavior
Limit value:
Off
Volume flow
Mass flow
Corrected volume flow
Flow velocity
Conductivity
Corrected conductivity
Totalizer 1-3
Temperature
Electronic temperature
Flow direction monitoring
Status
Empty pipe detection
Low flow cut off
User configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable
I/O) during device commissioning.
The following inputs and outputs are available for assignment:
Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Pulse/frequency/switch output
Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Status input
The technical values correspond to those of the inputs and outputs described in this
section.
Signal on alarm Depending on the interface, failure information is displayed as follows:
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
0 to 20 mA
Failure mode Choose from:
Maximum alarm: 22 mA
Freely definable value between: 0 to 20.5 mA
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses