Technical data Liquiline CM44P
188 Endress+Hauser
PROFIBUS DP/RS485
Signal encoding EIA/TIA-485, PROFIBUS DP-compliant acc. to IEC 61158
Data transmission rate 9.6 kBd, 19.2 kBd, 45.45kBd, 93.75 kBd, 187.5 kBd, 500 kBd,
1.5 MBd, 6 MBd, 12 MBd
Galvanic isolation Yes
Connectors Spring terminal (max. 1.5 mm), bridged internally (Tfunction),
optional M12
Bus termination Internal slide switch with LED display
Modbus RS485
Signal encoding EIA/TIA-485
Data transmission rate 2,400, 4,800, 9,600, 19,200, 38,400, 57,600 and 115,200
baud
Galvanic isolation Yes
Connectors Spring terminal (max. 1.5 mm), bridged internally (Tfunction),
optional M12
Bus termination Internal slide switch with LED display
Ethernet and Modbus TCP
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 10/100 MBd
Galvanic isolation Yes
Connection RJ45
IP address DHCP (default) or configuration via menu
EtherNet/IP
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 10/100 MBd
Galvanic isolation Yes
Connection RJ45
IP address DHCP (default) or configuration via menu
PROFINET
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 100 MBd
Galvanic isolation Yes
Connection RJ45
Name of station Via DCP protocol using the configuration tool (e.g. Siemens
PRONETA)
IP address Via DCP protocol using the configuration tool (e.g. Siemens
PRONETA)