Liquiline CM44P Operation
Endress+Hauser 89
Menu/Setup/Outputs/Alarm relay or relay at channel no.
Function Options Info
Function Selection
Off
Limit switch
Controller
Diagnostics
Cleaning
(sensor)
Formula
(sensor)
Factory setting
Alarm relays:
Diagnostics
Other relays:
Off
The following functions depend on the option
selected.
These versions are illustrated individually in the
following sections to provide a clearer
understanding of the options.
Function = Off
Switches off the relay function and means no
further settings are required.
Outputting the status of a limit switch
Function = Limit switch
Function Options Info
Source of data Selection
Limit switch 1 ... 8
Factory setting
None
Select the limit switch via which the status of the
relay is to be output.
The limit switches are configured in the menu:
Setup/Additional functions/Limit switches.
Use the ALL and NONE soft keys to select
or deselect all the limit switches in one go.
Hold behavior Selection
Freeze last value
Fixed value
Ignore
Factory setting
Ignore
Outputting the manipulated variable of a controller
To output a controller manipulated variable via a relay, the relay is modulated. The relay is
energized (pulse, t
1
) and is then de-energized (interval, t
0
).
Function = Controller
Function Options Info
Source of data Selection
None
Controller 1
Controller 2
Factory setting
None
Select the controller that should act as the
data source.
Operating mode Selection
PWM
PFM
Factory setting
PWM
PWM=pulse width modulation
PFM=pulse frequency modulation