Micropilot FMR62
14 Endress+Hauser
Output
Output signal
HART
• Signal coding:
FSK ±0.5 mA over current signal
• Data transmission rate:
1 200 Bit/s
• Galvanic isolation:
Yes
Bluetooth® wireless technology
• Device version:
Order code 610 "Accessory mounted", option NF "Bluetooth"
• Operation / configuration:
Via the SmartBlue app
• Range under reference conditions:
> 10 m (33 ft)
• Encryption:
Encrypted communication and password encryption prevent incorrect operation by unauthorized
persons
Switch output
For HART devices, the switch output is available as an option.
• Function:
Open collector switch output
• Switching behavior:
Binary (conductive or non-conductive), switches when the programmable switch-on point/switch-
off point is reached
• Failure mode:
Non-conductive
• Electrical connection data:
U = 16 to 35 V
DC
, I = 0 to 40 mA
• Internal resistor:
R
I
< 880 Ω
The voltage drop at this internal resistor must be taken into account when planning the
configuration. For example, the resulting voltage at a connected relay must be sufficient to switch
the relay.
• Insulation voltages:
Floating, insulation voltage 1 350 V
DC
in relation to power supply and 500 V
AC
ground
• Switch point:
User-programmable, separate for switch-on point and switch-off point
• Switching delay:
User-programmable in the 0 to 100 s range, separate for switch-on point and switch-off point
• Scan rate:
Corresponds to the measuring cycle
• Signal source / device variables:
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Diagnostic values, advanced diagnostic blocks
• Only for active interface measurement
• Number of switch cycles:
Unlimited