Micropilot FMR62
Endress+Hauser 35
Installation in the bypass
A0042914
17 Installation in the bypass
1 Tank connectors
Measurements can be performed through an open full bore ball valve without any problems.
Recommendations for the bypass
• Metal (no enamel plastic or enamel liner).
• Constant diameter.
• Select an antenna that is as big as possible. Recommendation, use the 80mm/3" antenna.
• Difference in diameter between antenna and inner diameter of the bypass as small as possible.
• At transition points, e.g. when a ball valve is used or individual pipe segments are joined, any gaps
that occur should not exceed 1 mm (0.04 in).