Installation conditions Orientation - Liquid media
A
1 2 3
A0016882
Recommended distance A wall - nozzle outer edge: ~ 1/6 of the vessel diameter. However, the
device must not under any circumstances be mounted closer than 15 cm (5.91 in) to the tank wall.
Not in the center (2) as interference can cause signal loss.
Not above the filling curtain (3).
The use of a weather protection cover (1) is recommended to protect the transmitter from direct
sunlight or rain.