Micropilot FMR62
36 Endress+Hauser
100%
0%
200 (7.87)
3
3
1
C
2
2
1 (0.04)
A
B
4
200 (7.87)
200 (7.87)
200 (7.87)
A0042915
 18 Example of bypass design. Unit of measurement mm (in)
A Micropilot FMR62; 80mm/3" antenna
B Full bore ball valve
C Minimum distance to upper connecting pipe: 400 mm (15.7 in)
1 e.g. welding neck flange DIN2633
2 Diameter of connecting pipes as small as possible
3 Do not weld through the pipe wall; the inside of the pipe must remain smooth.
4 Opening diameter of ball valve must always correspond to the pipe diameter. Avoid edges and constrictions.
Reduced measuring accuracy can be expected in the area of the tank connectors (~
±20 cm (7.87 in)).
Container with heat
insulation
1
2
A0032207