Commissioning Proline Promass I 300 PROFINET
104 Endress+Hauser
Parameter Prerequisite Description User interface /
Selection / User
entry
Factory setting
• Index suspended
bubbles
*
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed current
Country-specific:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
0/4 mA value In the Current span parameter
(→ 104), one of the
following options is selected:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter 4 mA value. Signed floating-point
number
Country-specific:
• 0 kg/h
• 0 lb/min
20 mA value One of the following options is
selected in the Current span
parameter (→ 104):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current The Fixed current option is
selected in the Current span
parameter (→ 104).
Defines the fixed output
current.
0 to 22.5 mA 22.5 mA
Damping output 1 to n A process variable is selected
in the Assign current output
parameter (→ 103) and
one of the following options is
selected in the Current span
parameter (→ 104):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Set reaction time for output
signal to fluctuations in the
measured value.
0.0 to 999.9 s –
Failure mode A process variable is selected
in the Assign current output
parameter (→ 103) and
one of the following options is
selected in the Current span
parameter (→ 104):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Define output behavior in
alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
–
Failure current The Defined value option is
selected in the Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA 22.5 mA