Commissioning Proline Promass I 300 PROFINET
104 Endress+Hauser
Parameter Prerequisite Description User interface / 
Selection / User
entry
Factory setting
Index suspended
bubbles
*
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
4...20 mA (4...
20.5 mA)
0...20 mA (0...
20.5 mA)
Fixed current
Country-specific:
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
0/4 mA value In the Current span parameter
(→  104), one of the
following options is selected:
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4... 20.5 mA)
0...20 mA (0... 20.5 mA)
Enter 4 mA value. Signed floating-point
number
Country-specific:
0 kg/h
0 lb/min
20 mA value One of the following options is
selected in the Current span
parameter (→  104):
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4... 20.5 mA)
0...20 mA (0... 20.5 mA)
Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current The Fixed current option is
selected in the Current span
parameter (→  104).
Defines the fixed output
current.
0 to 22.5 mA 22.5 mA
Damping output 1 to n A process variable is selected
in the Assign current output
parameter (→  103) and
one of the following options is
selected in the Current span
parameter (→  104):
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4... 20.5 mA)
0...20 mA (0... 20.5 mA)
Set reaction time for output
signal to fluctuations in the
measured value.
0.0 to 999.9 s
Failure mode A process variable is selected
in the Assign current output
parameter (→  103) and
one of the following options is
selected in the Current span
parameter (→  104):
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4... 20.5 mA)
0...20 mA (0... 20.5 mA)
Define output behavior in
alarm condition.
Min.
Max.
Last valid value
Actual value
Defined value
Failure current The Defined value option is
selected in the Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA 22.5 mA
* Visibility depends on order options or device settings