Proline Promass I 300 PROFINET Commissioning
Endress+Hauser 137
Parameter overview with brief description
Parameter Prerequisite Description Selection / User entry / 
User interface
Assign simulation process variable Select a process variable for the
simulation process that is activated.
Off
Mass flow
Volume flow
Corrected volume flow
*
Target mass flow
*
Carrier mass flow
*
Target volume flow
*
Carrier volume flow
*
Target corrected volume
flow
*
Carrier corrected volume
flow
*
Density
Reference density
*
Temperature
Dynamic viscosity
*
Kinematic viscosity
*
Temp. compensated
dynamic viscosity
*
Temp. compensated
kinematic viscosity
*
Concentration
*
Process variable value A process variable is selected in the
Assign simulation process variable
parameter (→  137).
Enter the simulation value for the
selected process variable.
Depends on the process
variable selected
Status input simulation 1 to n Switch simulation of the status input on
and off.
Off
On
Input signal level 1 to n In the Status input simulation
parameter, the On option is selected.
Select the signal level for the simulation
of the status input.
High
Low
Current input 1 to n simulation Switch simulation of the current input
on and off.
Off
On
Value current input 1 to n In the Current input 1 to n simulation
parameter, the On option is selected.
Enter the current value for simulation. 0 to 22.5 mA
Current output 1 to n simulation Switch the simulation of the current
output on and off.
Off
On
Value current output 1 to n In the Current output 1 to n
simulation parameter, the On option is
selected.
Enter the current value for simulation. 3.59 to 22.5 mA
Frequency output simulation 1 to n In the Operating mode parameter, the
Frequency option is selected.
Switch the simulation of the frequency
output on and off.
Off
On
Frequency value 1 to n In the Frequency output simulation
1 to n parameter, the On option is
selected.
Enter the frequency value for the
simulation.
0.0 to 12 500.0 Hz
Pulse output simulation 1 to n In the Operating mode parameter, the
Pulse option is selected.
Set and switch off the pulse output
simulation.
For Fixed value option: Pulse
width parameter (→  106)
defines the pulse width of the
pulses output.
Off
Fixed value
Down-counting value
Pulse value 1 to n In the Pulse output simulation 1 to n
parameter, the Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65 535
Switch output simulation 1 to n In the Operating mode parameter, the
Switch option is selected.
Switch the simulation of the switch
output on and off.
Off
On
Switch status 1 to n Select the status of the status output for
the simulation.
Open
Closed