11 Operation via FOUNDATION Fieldbus Proline Prowirl 72 FOUNDATION Fieldbus
90 Endress + Hauser
System Unit -
Volume Flow
AUTO - OOS Use this function to select the unit for the volume flow (volume/time).
The unit you select here is also valid for:
Simulation
Low flow cut off
Display value (local display)
! Note!
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options:
Metric:
Cubic centimeter cm³/time unit
–Cubic decimeter dm³/time unit
–Cubic meter /time unit
Milliliter ml/time unit
–Liter l/time unit
Hectoliter hl/time unit
Megaliter Ml/time unit MEGA
US:
Cubic centimeter cc/time unit
Acre foot af/time unit
Cubic foot ft³/time unit
Fluid ounce ozf/time unit
Gallon US gal/time unit
Mega gallon US Mgal/time unit
Barrel (normal fluids: 31.5 gal/bbl)
US bbl/time unit NORM.
Barrel (beer: 31.0 gal/bbl) US bbl/time unit BEER
Barrel (petrochemicals: 42.0 gal/bbl)
US bbl/time unit PETR.
Barrel (filling tanks: 55.0 gal/bbl) US bbl/time unit TANK
Imperial:
Gallon imp. gal/time unit
Mega gallon imp. Mgal/time unit
Barrel (beer: 36.0 gal/bbl) imp. bbl/time unit BEER
Barrel (petrochemicals: 34.97 gal/bbl)
imp. bbl/time unit PETR.
Factory setting:
Depends on country (metric system units, Page 121, or US units,
Page 122)
System Value -
Calc. Mass Flow
Read only The calculated mass flow appears on the display.
The calculated mass flow is calculated using the measured volume flow
and the value entered in the "Process Param. – Operating Density"
parameter (Page 94). A fixed value is used for the calculation
(specified operating density). For this reason only select this process
variable if the process conditions are known and do not change.
! Note!
The unit is displayed in the "System Unit - Calc. Mass Flow" parameter.
(Page 91)
Transducer Block "Flow" (Endress+Hauser parameters) / base index 500
Parameter Write access for
operating mode
(MODE_BLK)
Description