11 Operation via FOUNDATION Fieldbus Proline Prowirl 72 FOUNDATION Fieldbus
90 Endress + Hauser
System Unit -
Volume Flow
AUTO - OOS Use this function to select the unit for the volume flow (volume/time).
The unit you select here is also valid for:
• Simulation
• Low flow cut off
• Display value (local display)
! Note!
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options:
Metric:
– Cubic centimeter cm³/time unit
–Cubic decimeter dm³/time unit
–Cubic meter m³/time unit
– Milliliter ml/time unit
–Liter l/time unit
– Hectoliter hl/time unit
– Megaliter Ml/time unit MEGA
US:
– Cubic centimeter cc/time unit
– Acre foot af/time unit
– Cubic foot ft³/time unit
– Fluid ounce ozf/time unit
– Gallon US gal/time unit
– Mega gallon US Mgal/time unit
– Barrel (normal fluids: 31.5 gal/bbl)
US bbl/time unit NORM.
– Barrel (beer: 31.0 gal/bbl) US bbl/time unit BEER
– Barrel (petrochemicals: 42.0 gal/bbl)
US bbl/time unit PETR.
– Barrel (filling tanks: 55.0 gal/bbl) US bbl/time unit TANK
Imperial:
– Gallon imp. gal/time unit
– Mega gallon imp. Mgal/time unit
– Barrel (beer: 36.0 gal/bbl) imp. bbl/time unit BEER
– Barrel (petrochemicals: 34.97 gal/bbl)
imp. bbl/time unit PETR.
Factory setting:
Depends on country (metric system units, Page 121, or US units,
Page 122)
System Value -
Calc. Mass Flow
Read only The calculated mass flow appears on the display.
The calculated mass flow is calculated using the measured volume flow
and the value entered in the "Process Param. – Operating Density"
parameter (Page 94). A fixed value is used for the calculation
(specified operating density). For this reason only select this process
variable if the process conditions are known and do not change.
! Note!
The unit is displayed in the "System Unit - Calc. Mass Flow" parameter.
(Page 91)
Transducer Block "Flow" (Endress+Hauser parameters) / base index 500
Parameter Write access for
operating mode
(MODE_BLK)
Description