Proline Prowirl 72 FOUNDATION Fieldbus 11 Operation via FOUNDATION Fieldbus
Endress + Hauser 87
11. 4 FOUNDATION Fieldbus parameters
The following table lists all the specified FOUNDATION Fieldbus parameters of the Transducer
Blocks.
The Endress+Hauser-specific parameters are described as of Page 89.
FOUNDATION Fieldbus parameters (Transducer Blocks)
Parameter Write access for
operating mode
(MODE_BLK)
Description
ST_REV Read only The revision status of the static data appears on the display.
! Note!
The revision status parameter is incremented with every change of the
static data.
TAG_DESC AUTO - OOS Use this function to enter a user-specific text of max. 32 characters for
unique identification and assignment of the block.
Factory setting:
(_____) no text
STRATEGY AUTO - OOS Parameter for grouping and thus faster evaluation of blocks. Grouping is
carried out by entering the same numerical value in the STRATEGY
parameter of each individual block.
Factory setting:
0
! Note!
These data are neither checked nor processed by the Transducer Blocks.
ALERT_KEY AUTO - OOS Use this function to enter the identification number of the plant unit.
This information can be used by the fieldbus host system for sorting
alarms and events.
User input:
1 to 255
Factory setting:
0
MODE_BLK AUTO - OOS For displaying the current (Actual) and the desired (Target) operating
mode of the relevant Transducer Block, the permitted modes supported
by the Transducer Block in question (Permitted) and the normal
operating mode (Normal).
Display:
AUTO
OOS
! Note!
The Transducer Blocks support the following operating modes:
• AUTO (automatic mode):
the block is executed.
• OOS (out of service):
the block is in the "out of service" mode.