EasyManua.ls Logo

ESAB Mig 4002cw - Page 39

ESAB Mig 4002cw
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-- 39 --
1sxx02cw
Fault
code
Description
4
5 V power supply too low.
The unregulated power supply voltage is too low: the smoothing capacitors cannot
keep the voltage up enough for the processor to continue to operate. The processor
stops all normal activities, expecting to be shut down.
Action: Turn off the mains power supply to reset the unit. If the fault persists, check
the power supply to circuit board CB0.
5
Choppers module rectifier DC voltage to low.The DC voltage on rectifier to low -- to
weak power supply (high inductance of the supply).
Action: See also pre--charging circuit.
6
High temperature
Thermal overload cutout B1 or B2. The power source is stopped, and cannot be
restarted until the cutout has reset.
Possible causes: Overloading, fan not working properly, cooling air inlets or outlets
blocked or obstructed or dirt on the heat exchanger.
8
+15 V power supply on circuit board CB0
The voltage is too high or too low: it must be within the range 14.1 -- 15.9 V. This
fault does not disable any functions.
9
--15 V power supply on circuit board CB0.
The voltage is too high or too low: it must be within the range 14.2 -- 16.4 V. This
fault does not disable any functions.
10
+24 V power supply on circuit board CB0.
The voltage is too high or too low: it must be within the range 22.1 -- 26.0 V.
12
Communication error (warning)
The load on the system CAN bus is temporarily too high, or there is electric noise on
the bus.
Action: Check the equipment to ensure that only one wire feed unit and/or remote
control unit are connected. See also section CB0 ’The CAN bus’.
15
Lost messages
The bus CAN controller indicates that a message has been lost. No functions are
disabled by this fault.
Action: Check that all units are correct connected to the CAN bus. See also section
CB0 ’The CAN bus’.
16
High open--circuit voltage
The open--circuit voltage has exceeded 113 V for more than one second. The power
source is turned off and cannot be restarted. Turn off the mains power supply to
reset the unit.
Action: Turn off the mains power supply to reset the unit.
22
Transmitter buffer overflow
The control board is unable to transmit information to the other units at a sufficiently
high speed.
Action: A break in the bus line can cause this fault. Check the CAN cabling. Turn off
themains power supply to reset the unit.

Table of Contents