Error Messages 59
AF Dim Removed
<Dimmer Nr>
AF detects that a dimmer has been
removed
Reinsert dimmer; check dimmer module
AF Bkr Trip
<Dimmer Nr>
AF detects that a dimmer circuit
breaker has tripped
Reset circuit breaker; check dimmer module
AF RCD Trip
<Dimmer Nr>
AF detects that a dimmer circuit with
RCD has tripped due to earth leakage
Reset circuit breaker; check dimmer module and
load
AF Load High
<Dimmer Nr>
AF detects that the current load on a
circuit is higher than the recorded load
Check load/lamps
AF Load Low
<Dimmer Nr>
AF detects that the current load on a
circuit is lower than the recorded load
Check load/lamps
AF No Load
<Dimmer Nr>
AF detects that there is no load on a
circuit
Check load/lamps
Dim Overtemp
<Dimmer Nr>
An overtemperature condition has
been detected on a dimmer module
Clear the error from the home screen and see if it
returns.
Check rack cooling fan is running and that room
is in recommended temperature range.
If normal temp, replace module.