PLC RESOURCES
Counters
6.
(SOFT M: V15.3X)
(S
OFT T: V16.3X)
·283·
Count value (C)
This output indicates the value of the internal counter count. It is referred to by the letter "C" followed
by the counter number, for example: C1, C25, C102, etc.
Although when written C123 it coincides with the status output, both are different and, are used in
different types of instructions.
In binary type instructions function C123 makes reference to the counter’s logic status.
C123 = M100 Assigns mark to M100 the status (0/1) of counter 123.
In arithmetic and function comparison instructions C123 makes reference to the internal counter
count.
The PLC has a 32-bit variable to store the count of each counter.
I2 = MOV C123 R200
Transfers the count of C123 to register R200.
CPS C123 GT 1000 = M100
Compares whether the count of C123 is greater than 1000. If so, it activates mark M100.