Commissioning
39
Value Description
RISING Factory setting: the setpoint position is increased with a rising setpoint
value.
FALLING The setpoint position is increased with a falling setpoint value.
Tab. 28: Setpoint direction
falling
rising
Target position [%]
Setpoint [%]
Fig. 25: Setpoint direction
Type of curve
The ‘Type of curve’ parameter defines the characteristic of the transmission characteristic curve
between setpoint value and setpoint position. The transmission characteristic curve is used to correct
the operating characteristic curve in order to guarantee a proportional flow relationship between the
setpoint value and the setpoint position.
Value Description
linear Factory setting: linear characteristic curve
1:25 Equal-percentage characteristic curve
1:33
1:50
25:1 Inverse equal-percentage characteristic curve
33:1
50:1
user defined User-defined characteristic curve
Tab. 29: Type of curve