BURNERLOGIX MESSAGES
Table 25:
DEC
HEX
BURNERLOGIX MESSAGES
1
1
H
T16 M-D LIMIT OPEN - AUTO
2
2
H
HOLD FALSE FLAME- STANDBY
3
3
R
LOW FIRE PURGE
4
4
H
HOLD M-8 LIMIT OPEN- PURGE
5
5
H
See Interlock Annunciation Message Table
6
6
H
T16 M-D LOW LIMIT - AUTO
7
7
L
LOCKOUT FLAME FAIL - PTFI
8
8
H
T16 INPUT
9
9
H
HOLD M-D LIMIT OPEN
10
A
R
IGNITION TIMING - PTFI
11
B
C
CHECK FLAME SIGNAL - MTFI
12
C
R
FLAME SIGNAL - AUTO
13
D
R
CYCLE COMPLETE - POST PURGE
14
E
R
L1-3 OPEN
15
F
H
T21 INPUT (LGP)
16
10
L
LOCKOUT M-D LIMIT OPEN - PTFI
17
11
L
LOCKOUT M-8 LIMIT OPEN
18
12
L
LOCKOUT M-D LIMIT OPEN
19
13
L
LOCKOUT FLAME FAIL - MTFI
20
14
L
LOCKOUT FALSE FLAME
21
15
L
LOCKOUT 3-P INTLK OPEN (PURGE)
22
16
L
LOCKOUT 3-P INTLK CLOSED
23
17
H
HOLD 3-P INTLK CLOSED - STANDBY
24
18
H
HIGH FIRE PURGE
25
19
L
LOCKOUT M-D LIMIT OPEN - MTFI
26
1A
L
LOCKOUT 3-P INTLK OPEN -AUTO
27
1B
L
LOCKOUT 3-P INTLK OPEN - MTFI
28
1C
L
LOCKOUT 3-P INTLK OPEN - PTFI
29
1D
L
LOCKOUT T13 FVES OPEN
30
1E
L
LOCKOUT 3-P INTLK OPEN - PREPURGE
31
1F
C
CHECK FLAME SIGNAL - PTFI
32
20
C
CHECK M-8 HI LIMIT (HI FIRE PURGE)
33
21
C
CHECK M-D LOW LIMIT (LO FIRE START)
34
22
R
FLAME SIGNAL- PTFI
35
23
C-H
HOLD T21 (LGP) or CHECK LOW FIRE SIGNAL - AUTO
36
24
R
FLAME SIGNAL - MTFI
37
25
L
LOCKOUT FLAME FAIL (AUTO)
38
26
H
HOLD 3-P INTLK OPEN - PREPURGE
39
27
L
LOCKOUT FUEL VALVE STATE CHANGE
104
68
R
LEARNING FLAME (PTFI and AUTO)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fireye BurnerLogiX YB110 and is the answer not in the manual?

Fireye BurnerLogiX YB110 Specifications

General IconGeneral
BrandFireye
ModelBurnerLogiX YB110
CategoryComputer Hardware
LanguageEnglish

Related product manuals