Table 2: LOAD RATINGS
Terminal
Typical Load
A. Maximum Rating
@120V-50/60 Hz
B. Maximum Rating
@230V-50/60 Hz
C. Alternate Rating
M
Burner/Blower Motor
9.8 F.L.A. *
58 L.R.A.
4.0 F.L.A. *
20 L.R.A.
240 VA Pilot Duty
(Motor Starter Coil)
10-11-12-X
Modulator
125 VA Pilot Duty
A
Alarm
50 VA Pilot Duty
Terminal ratings may be selected from either column A or C for 120 VAC or from either column B or C for 30 VAC:
(select the rating from the column which best applies to the connected load on that terminal).
* F.L.A. = full load amps; L.R.A = locked rotor amps
Combination of fuel and igniter terminals
Combination No.
Pilot Fuel
Trm 6
Main
Trm 7
Ignition
Trm 5
Delayed Valve
Trm W
1
C
E
No Load
No Load
2
B
E
No Load
No Load
3
No Load
E
No Load
B
4
E
E
A
No Load
5
No Load
E
A
E
6
D
E
A
No Load
7
D
D
A
D
8
No Load
D
A
No Load
For YP148/YP184 programmers, Ignition (Terminal W) - 4.5 A, Pilot (Terminal 5) - 2A Pilot Duty,
Main Valve 1 (Terminal 6) - 2A Pilot Duty, Main Valve 2 (Terminal 7) - 2A Pilot Duty
Refer YP148/YP184 wiring diagram for more details on terminals.
Composition of each combination
A
B
C
D
E
4.5A Ignition
@120 VAC
50 VA Pilot Duty
plus 4.5A ignition@
120 VAC
180 VA Ignition plus
motor valves with: 660
VA inrush, 360 VA
open, 250 VA hold.
2A Pilot Duty
@120 VAC
65 VA Pilot Duty plus
Motor valves with: 700
VA open 250 VA hold.
2.2A Ignition
@230 VAC
50 VA Pilot Duty
plus 2.2A ignition
@230 VAC
1A Pilot Duty
@230 VAC
Maximum connected load must not exceed 2000 VA
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar
devices whose inrush current is approximately the same as their running current.
VA Pilot Duty ratings permit the connection of relays, solenoid valves, lamps, etc. who’s total
operating load does not exceed the published rating and whose total inrush current does not
exceed 10 times the rating.
Running and locked rotor ratings are intended for motors. VA and VA Pilot Duty loads may be
added to a motor load provided the total load does not exceed the published rating.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fireye BurnerLogiX YB110 and is the answer not in the manual?

Fireye BurnerLogiX YB110 Specifications

General IconGeneral
BrandFireye
ModelBurnerLogiX YB110
CategoryComputer Hardware
LanguageEnglish

Related product manuals