Table 4‐14. Transducer Block Parameter Definitions (Continued)
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
PRESS_CAL
46
Supply Pressure Scale
SUPP_PRESS_SCALE
46.1 RW
MAN
OOS
> 0 CAL Data Type: Float
Supply Pressure Offset
SUPP_PRESS_OFFSET
46.2 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure A Scale
PRESS_A_SCALE
46.3 RW
MAN
OOS
> 0 CAL Data Type: Float
Pressure A Offset
PRESS_A_OFFSET
46.4 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure B Scale
PRESS_B_SCALE
46.5 RW
MAN
OOS
> 0 CAL Data Type: Float
Pressure B Offset
PRESS_B_OFFSET
46.6 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure IP Bias
PRESS_IP_BIAS
46.7 RW
MAN
OOS
0-100% 70% CAL Data Type: Float
Pressure MLFB Bias
PRESS_MLFB_BIAS
46.8 RW
MAN
OOS
0-100% 50% CAL Data Type: Float
PRESS_TUNE
47
Pressure Cutoff Hi
PRESS_CUTOFF_HI
47.1 RW
MAN
OOS
-25 -125%,
> CUTOFF_LO
99.50% SETUP Data Type: Float
Pressure Cutoff Lo
PRESS_CUTOFF_LO
47.2 RW
MAN
OOS
-25 -125% < CUTOFF_HI 0.50% SETUP Data Type: Float
Pressure Proportional Gain
PRESS_PROP_GAIN
47.3 RW
MAN
OOS
> = 0, < 32 2.2 SETUP
Data Type: Float
Proportional gain
Pressure Integral Gain
PRESS_INTEG_GAIN
47.4 RW
MAN
OOS
> = 0, < 32 0.1 SETUP
Data Type: Float
Integral resets per second
Pressure Rate Gain
PRESS_RATE_GAIN
47.5 RW
MAN
OOS
> = 0, < = 512 0 SETUP
Data Type: Float
Derivative gain
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
47.6 RW
MAN
OOS
= 0%, < = 2.0% 0.25% SETUP
Data Type: Float
Integrator Deadzone, 1/2 width
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
47.7 RW
MAN
OOS
> = 0%, < = 100%,
>INTEG_LO
20% SETUP
Data Type: Float
Integrator limits
Pressure Integral Limit LO
PRESS_INTEG_LO_LIM
47.8 RW
MAN
OOS
< = 0%, > = -100%,
<INTEG_HI
-20% SETUP
Data Type: Float
Integrator limits
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
47.9 RW
MAN
OOS
>= -100%, < = 100% 12% Not used by the DVC6200f
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
47.10 RW
MAN
OOS
>= -100%, < = 100% -12% Not used by the DVC6200f
Pressure MLFB Gain
PRESS_MLFB_GAIN
47.11 RW
MAN
OOS
> 0, < = 100 35 SETUP Data Type: Float
Temperature
TEMPERATURE
48 RO N/A N/A N/A
Data Type: Float
Electronics temperature - Controls
AI channel 11
Target Travel
TRAVEL_TARGET
49 RO
Status
STATUS
49.1 RO
MAN
OOS
N/A
Data Type: DS‐65
In Travel Control:
Setpoint for valve
travel in %, post characterization.
In Pressure Control:
Setpoint for
implied valve travel as a % or
pressure range, post
characterization.
Value
VALUE
49.2 RO
MAN
OOS
N/A
Input Characterization
INPUT_CHAR
50 RW
MAN
OOS
1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom
1=Linear SETUP Data Type: Enum (Uint8)
-Continued-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200f and is the answer not in the manual?

Fisher FIELDVUE DVC6200f Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC6200f
CategoryController
LanguageEnglish

Related product manuals