FLIRCM85USERMANUALDocumentIdentifier:CM85‐en‐US_AB
31
Table7.8Activepower:watts(DC/AC)
Function
Range
1
Accuracy
DCW
9.999kW(10V,5Amin) ±(3%+0.05kW)
99.99kW(10V,5Amin) ±(3%+0.5kW)
999.9kW(10V,5Amin) ±(3%+10dgt)
ACW
9.999kW(10V,5Amin)
±(3%+10dgt)99.99kW(10V,5Amin)
999.9kW(10V,5Amin)
1.TherangeisdeterminedbytheV/Arange(9.999kW:100V,100A;99.99kW:1000V,100A,or
100V,1000A;999.9kW:1000V,1000A).
Overloadprotection:1000V
rms
,1000A
rms
.
Accuracydefinedfor:
ACW:
Sinewaves,ACV≥
10V
rms
,ACA≥5A
rms
.
Frequency50–60Hz,PF=1.00.
DCW:DCV≥10V,DCA≥5A.
Table7.9Powerfactor
Function Range Accuracy
PF –1.00to0.00to+1.00 ±3°±1dgt
Overloadprotection:1000V
rms
,1000A
rms
.