29
TRVL range Setting end positions
0%=0.0% Select Out of Service.
Set percentage value
for desired end position
(e.g. 3%).
Set 0% Select In Service.
Connect calibrator.
Move forward to desired
end position (0%) and
press OK.
100%=100.0% Select Out of Service.
Set percentage value for
desired end position
(e.g. 97%).
Set 100% Select In Service.
Connect calibrator. Move
forward to desired end
position (100%) and
press OK.
Trvl ctrl Behavior at set end
position
Set low Choose between Free (go
to mechanical stop),
Limit (stop at set end
position), and Cut off (go
directly to mechanical
stop at set end position).
Set high Similar to Set low.
Values Select position for Cut off
and Limit at the
respective end positions.
Passcodes Setting passcodes for
various functions
Full menu Passcode for access to
full menu.
Write prot Passcode for removing
write protect.
Expert Passcode for access to
Expert menu (TUNING).
Fact set Passcode to return to
default values applicable
when positioner was
delivered.
Numbers between 0000 and 9999 can be
used as passcodes. 0 = no passcode required.
Appearance On display
Language Select menu language.
Units Select units.
Def. Display
Select value(s) to be
displayed during service.
The display reverts to
this value 10 minutes
after any change is made.
Start menu
Start in Basic menu or
Full menu.
Orient
Orientation of text on
display.
Par mode
Display of control para-
meters such as P, I, D or
K, Ti, Td.
Devicedata
HW rew
SW rew
General parameters
.
Capability
HART
Menu with HART para-
meters. Only amendable
with HART communi-
cator. It is possible to read
from display.
Profibus PA/DP
Status
Indicates present status
Device ID
Serial number
Address
1-126
Tag
Allotted ID
Descriptor
ID description
Date
SW release date
Failsafe
Value = preset pos
Time = Set time +10sec=
time before movement
Valve act = failsafe
(preset pos) or last value
(present pos)
Alarm out= On/Off
Foundation Fieldbus
Device ID
Serial number
Nod address
Address on the bus
provided by the DCS
system
TAG–PD_TAG
Name provided by the
DCS system
Descriptor
PMV D3 positioner
Date
SW release date
Sim jumper
Simulate jumper, FF
simulation functionality
activated = ON
PMV D3 Digital Positioner FCD PMENIM0001-06 A5 09/16