7
Integrated
Gauge block
The figure shows the PMV D3
with the cover removed.
4. Variants
PMV D3 General purpose
The PMV D3 digital positioner has an easy
to use user interface with 5 pushbuttons and
local graphic LCD display. Communication
options include 4-20mA HART, Foundation
Fieldbus and Profibus PA. All PMV D3 posi-
tioners are available with Feedback, Fail Freeze
(Fail in last position and hold when power
is lost), 270-degree rotation (for extended
travel) and gauge block.
PMV D3 Intrinsically safe
The PMV D3 digital positioner is available in
intrinsically safe version for installation in
hazardous areas. The intrinsically safe PMV
D3 has all the same features and options as
the general purpose version, gauge block,
local graphic LCD display and feedback option
etc. Communication with Hart, Profibus and
Foundation Fieldbus is possible.
ATEX:
II 1G Ex ia IIC T4 Ga Ta:80 ˚C / IP66
Pressure sensors
Pressure sensors can be installed in the
pneumatic block in order to provide advanced
diagnostics in combination with ValveSight
software.
PMV D3 Explosion proof
The PMV D3 digital positioner is available
in explosion proof enclosure. The explosion
proof PMV D3 features the same easy to use
interface for local configuration as the general
purpose version. Communication with Hart,
Foundation Fieldbus and Profibus is possible.
Further features are gauge ports and local
graphic LCD display.
ATEX:
II 2G Ex d IIB+H
2
T6 Gb (-20°C to +60 °C)
II 2D Ex tb IIIC T100°C Db (-20°C to +80°C)
CSA, FM:
Class I, Div.1 Grps B, C, D
Class II, Div.1 Grps E, F, G
Class III, Div.1
T6, T5 / Type 4X
PMV D3 Digital Positioner FCD PMENIM0001-06 A5 09/16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flowserve PMV D3 and is the answer not in the manual?

Flowserve PMV D3 Specifications

General IconGeneral
BrandFlowserve
ModelPMV D3
CategoryController
LanguageEnglish

Related product manuals