32
Temp Alarm based on temperature
On/Off Temperature alarm on/off.
Low temp Temperature setting.
High temp Temperature setting.
Hysteresis Allowed hysteresis.
Alarm out Select ON/OFF offers output on terminals.
Valve act Behavior of valve when alarm is generated.
Valve act
No action Alarm generated only. Operations not affected.
Goto open C+ gives full pressure and valve moves to fully
open position. Positioner changes to position
Manual.
Goto close C- gives full pressure and valve moves to fully
closed position. Positioner changes to position
Manual.
Manual Valve stays in unchanged position. Positioner
moves to position Manual.
PMV D3 Digital Positioner FCD PMENIM0001-06 A5 09/16