EasyManua.ls Logo

Fluke PM6685 - Power Supply Troubleshooting

Fluke PM6685
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
erarchically designed in different levels, and troubleshooting can be
performed in any design level if the lower levels are OK. It is, there
-
fore, important to disconnect all options at the beginning of the trou
-
bleshooting procedure.
Power Supply
Connect the counter to line power.
Set the counter to STAND-BY mode.
Check that the voltage between J9 and J10 is in the range of
90 to 260 VAC, (see Fig. 5-2).
Check that the input voltage to the power module, U39 be
-
tween pin 1 and pins 4 and 5 on the bottom side of the PCA, is
120 to 375 VDC.
Move the jumper J16 to the DISCONNECT position.
Check the “STAND BY” voltages after the power module,
U39. Use for instance the screen around the input amplifier as
ground connection. There are also a number of ground pads on
the PCB available for this purpose.
*NOTE: If this voltage does not meet the above-mentioned
spec, and if it is not possible to adjust it, the output
resistances of the module must be checked.
To verify the Power Module proceed as follows:
If the primary fuse is broken, there is a short circuit in the
primary circuits. Use a DMM and try to locate the fault by
resistance measurements.
Disconnect L6 and check the resistance between pin 1 and
pins 4 and 5 on the power module. The DMM should not
show a short circuit. Put L6 back.
Check that the DC voltage between pin 1 and pins 4 and 5
on the power module is about Ö 2 times the input
AC-voltage. If not, use traditional troubleshooting tech
-
niques to locate the fault.
Remove the power cable from the counter.
Measure the resistances according to the table below.
If one of the above-mentioned measurements shows 0 W,
remove L7, L8, and L9 and use conventional troubleshoot
-
ing techniques to isolate the fault.
Measure the resistances according to the table below.
If the resistances deviate considerably from the values in the table,
the complete power module must be replaced.
Move jumper J16 to the CONNect position.
Connect the power cable to the counter.
Switch the counter ON.
Check the “POWER ON” voltages.
*NOTE: If the +5 V voltage is outside the specification, all
other levels will be wrong, since they are based on the
+5 V level.
If you find any fault, continue with traditional troubleshooting tech
-
niques and replace defective circuits. Also refer to Power Supply in
Chapter 4, Circuit Descriptions.
Troubleshooting 5-5
Power
Module
Fuse
TP23, +5
TP20, -5.2
TP22, +7
J10
J9
J4
J3
+5V adjust
6 14
1 5
TP21,+12V
TP15, +5
TP17, -7
J15
TP16, +15
Load
Disconnected
Connected
J21
J16
Fig. 5-2 Test points and trimmers for the power supply.
Test Points Voltage
TP15 +5.10V±10mV*
TP16 +14.8 V to +21 V
TP17 –12.5 V to –7.5 V
TP21 +12 V ± 0.5 V
Table 5-4 Standby voltages.
Test Pins Resistance
(GND) and TP15 (+5 V) »10 W
(GND) and TP16 (+15 V) »1.5 kW
(GND) and TP17 (–7 V) »270 W
Table 5-5 Output resistances.
Test Pins Resistance
10, 11 and 13, 14 »150 W
8 and 9 »1.5 kW
6 and 7 »270 W
Table 5-6 Output resistances.
Test Points Voltage
TP23 +5.06V±30mV*
TP20 5.2V±50mV
TP22 +7 V ± 100 mV
Table 5-7 Power-on voltages.

Other manuals for Fluke PM6685