EasyManua.ls Logo

Franklin Electric MonoDrive - Symptom Based Troubleshooting

Franklin Electric MonoDrive
184 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAINTENANCE
Troubleshooting
47
Symptom Based Troubleshooting
Condition Display Possible Cause Corrective Action
No Water
None
• No supply voltage
present
• Display board cable
disconnected or loose
• Verify cable connection between main control board and
display board
• If correct voltage is present, replace drive
Green
“---”
• Pressure sensor circuit
• Verify water pressure is below system set point
• If Pressure Input Board break-away tab is removed,
ensure auxiliary device is connected and closed circuit
• Jumper wires together at pressure sensor; if pump starts,
replace sensor
• If pump doesn’t start, check sensor connection at
Pressure Input Board; if loose, repair
• If pump doesn’t start, jumper sensor connection at
Pressure Input Board. If pump starts, replace wire
• If pump doesn’t start with sensor Pressure Input Board
connection jumpered, replace Pressure Input Board
• If pump doesn’t start with new Pressure Input Board,
replace drive
Red
Fault Code
• Fault detected
• Refer to
“Diagnostic Fault Codes” on page 43.
Green
Motor Frequency
• Drive and motor are
operating
• Loose switch or cable
connection
• Incorrect motor or pump
settings
• Motor may be running
backwards
• Gulping water at pump
inlet
• Verify Maximum Frequency setting. If this setting was
reduced below maximum value, increase
• Verify motor/pump ratings and match to motor/pump
settings on drive (DIP switch or Wi-Fi)
• Verify motor connections
• Frequency max, amps low, check for closed valve, or
stuck check valve
• Frequency max, amps high, check for hole in pipe
• Frequency max, amps erratic, check pump operation,
dragging impellers
• This is not a drive problem
• Check all connections
• Disconnect power, allow well to recover and retry
Pressure Fluctua-
tions (Poor Regu-
lation
Green
Motor Frequency
• Pressure sensor
placement and setting
• Pressure gauge
placement
• Pressure tank size and
pre-charge
• Leak in system
• Air in pump intake (lack
of submergence)
• System response setting
• Correct pressure sensor placement and settings
• Tank may be too small for system flow
• This is not a drive problem
• Disconnect power and check pressure gauge for drop
• Set deeper in the well or tank; install a flow sleeve with
airtight seal around drop pipe and cable
• If fluctuation is only on branches before sensor, enable
Steady Flow
• Change tank size configuration
• Reduce frequency output range
• Adjust System Response value

Table of Contents