EasyManua.ls Logo

Franklin Electric MonoDrive - Symptom Based Troubleshooting

Franklin Electric MonoDrive
184 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAINTENANCE
Troubleshooting
47
Symptom Based Troubleshooting
Condition Display Possible Cause Corrective Action
No Water
None
No supply voltage
present
Display board cable
disconnected or loose
Verify cable connection between main control board and
display board
If correct voltage is present, replace drive
Green
“---”
Pressure sensor circuit
Verify water pressure is below system set point
If Pressure Input Board break-away tab is removed,
ensure auxiliary device is connected and closed circuit
Jumper wires together at pressure sensor; if pump starts,
replace sensor
If pump doesn’t start, check sensor connection at
Pressure Input Board; if loose, repair
If pump doesn’t start, jumper sensor connection at
Pressure Input Board. If pump starts, replace wire
If pump doesn’t start with sensor Pressure Input Board
connection jumpered, replace Pressure Input Board
If pump doesn’t start with new Pressure Input Board,
replace drive
Red
Fault Code
Fault detected
Refer to
“Diagnostic Fault Codes” on page 43.
Green
Motor Frequency
Drive and motor are
operating
Loose switch or cable
connection
Incorrect motor or pump
settings
Motor may be running
backwards
Gulping water at pump
inlet
Verify Maximum Frequency setting. If this setting was
reduced below maximum value, increase
Verify motor/pump ratings and match to motor/pump
settings on drive (DIP switch or Wi-Fi)
Verify motor connections
Frequency max, amps low, check for closed valve, or
stuck check valve
Frequency max, amps high, check for hole in pipe
Frequency max, amps erratic, check pump operation,
dragging impellers
This is not a drive problem
Check all connections
Disconnect power, allow well to recover and retry
Pressure Fluctua-
tions (Poor Regu-
lation
Green
Motor Frequency
Pressure sensor
placement and setting
Pressure gauge
placement
Pressure tank size and
pre-charge
Leak in system
Air in pump intake (lack
of submergence)
System response setting
Correct pressure sensor placement and settings
Tank may be too small for system flow
This is not a drive problem
Disconnect power and check pressure gauge for drop
Set deeper in the well or tank; install a flow sleeve with
airtight seal around drop pipe and cable
If fluctuation is only on branches before sensor, enable
Steady Flow
Change tank size configuration
Reduce frequency output range
Adjust System Response value

Table of Contents

Other manuals for Franklin Electric MonoDrive

Related product manuals