RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
Page 57
FRONT PANEL
DISPLAY
58
77
78
76
5
75
74
73
72
71
70
69
68
67
66
65
64
63
62
61
60
59
57
56
55
53
54
52
51
50
49
48
46
47
45
43
44
42
41
40
5
USE BELDEN #8777 OR EQUAL (3 TWISTED PAIRS)
COLOR CODING SHOWN IS BELDEN #8777
RS 422 WIRING SHALL BE SEPARATE
FROM ALL OTHER WIRING
WIRED AT FRICK IF BOTH UNITS
ARE ON THE SAME SKID
NOTE:WHEN USING THE RS422 PORTS FOR
LEAD-LAG,THEYCANNOTBEUSEDFOR
ANY OTHER COMMUNICATIONS
12 COND RIBBON CABLE
STUD
GREEN
SET SW1 TO CORRECT VOLTAGE
NO CONNECTION ON 230
FOR GROUNDED CIRCUITS
TOROID
FERRITE
RING
REV D SBC ONLY
GREEN WIRE
WRAP WIRES THROUGH TOROID TWO (2)
TIMES, ALL IN THE SAME DIRECTION
STUD
KEY
1
1
PA D
P10
1
NEU
230
115
230
115
SW1
GND
P13
SBC
2
26 COND RIBBON CABLE
P1
P11
1
8
9
5
4
3
BLK
BLK
RED
8
9
5
GRN
4
3
SBC
RS422
PORT 1
UNIT "B"
SBC
RS422
PORT 1
UNIT "A"
WIRING FOR LEAD-LAG SEQUENCING
OPTIONAL
2
TEMPERATURE SENSOR WIRING TO BE #8760
BELDEN CABLE OR EQUAL. GROUND DRAIN WIRE
AT PANEL GROUND ONLY. INSULATE AT PROBE END
NOTE 2A:
SPECIFICATIONS FOR TEMP. CAPACITY CONTROL
TEMP PROBE-FRICK P/N - 111Q0280982
WELL FOR ABOVE, 3/4"MPT WELL CONNECTION,
1/2" FPT FOR CONNECTION BOX- P/N - 990A0014H01
HEAT TRANSFER COMPOUND-P/N - 111Q0831807
-WIRE AS SHOWN IN SEPARATE CONDUIT
FROM ALL OTHER WIRING
USE BELDEN #8761 CABLE OR EQUAL
-MOUNTING IN WELL IS DESIRABLE
USE HEAT TRANSFER COMPOUND
-TEMP PROBE SIZE- .188 DIA x 4" LONG
304 S.S.WITH (2) 24" LEADS
-SETPOINT RANGE: -50
OF.TO 100OF.
RXBELD4
MICRO PANEL ASSEMBLY WIRING DIAGRAM
MAINTENANCE
Revised 1/97

Table of Contents