System design
CAUTION!
Danger from connecting an electronic thermostat.
This would destroy the Ohmpilot or the connected load.
Use mechanical temperature switches.
CAUTION!
Danger due to connection of an incorrect load (e.g. fan heater).
This may result in destruction of the load.
Connect only purely resistive loads.
NOTE!
Phase control
The sum of all phases forms the basis for Ohmpilot control. The Ohmpilot is not
suitable for phase-accurate billing.
NOTE!
Ohmpilot and Fronius Datamanager 2.0 / Fronius Hybridmanager
Only one Ohmpilot can be connected per Fronius Datamanager 2.0 / Fronius Hy-
bridmanager.
NOTE!
Ohmpilot and dynamic power reduction
From software version 3.13.1-x of the Fronius Datamanager or 1.11.1-x of the
Fronius Hybridmanager, the Ohmpilot can be used together with dynamic power
reduction from 0-100%.
NOTE!
Use of other generation sources
Other generation sources can also be used in conjunction with the Fronius
Datamanager Box 2.0, e.g. CHP, third-party inverters, etc. Generated power and
consumption data cannot be acquired for other generation sources, so these fig-
ures cannot be displayed in Fronius Solar.web.
NOTE!
Backup power
Due to the high heat output, the Ohmpilot cannot be operated in backup power
situations.
Install the Ohmpilot outside the backup power circuit.
NOTE!
Calcification of the connected heating element
Calcification can occur with hard water, especially if the minimum temperature is
set above 60 °C. An annual inspection of the heating element is recommended.
Remove the heating element from the tank and remove the limescale;
do not scratch the surface of the heating element while doing so.