Installation
Stripping
lengths
Stripping lengths of terminals for
power stage set (L1, L2, etc.) and ter-
minals for data communication area (D
+, D-, PT1000)
Electrical con-
nection
IMPORTANT! Electrical connection work must be carried out by a specialist.
WARNING!
Danger from inadequate ground conductor connection.
This can result in severe personal injury or damage to property.
Install and connect the ground conductor connection in accordance with the
national specifications
NOTE!
Overvoltage from the grid
Overvoltage can damage the device
Equip the Ohmpilot with a type B16 A automatic circuit breaker and a resid-
ual current circuit breaker.
NOTE!
Cable length
The maximum cable length from the output of the Ohmpilot to the load (heating
element) must not exceed 5 metres due to electromagnetic compatibility.
NOTE!
Load connection
Only connect purely resistive loads.
When connecting a heating element, check the earthing of the boiler/buffer
and the heating system.
Observe the maximum permissible flow and hot water temperature when set-
ting the temperature on the heating element.
23