1
Open the Ohmpilot user interface (see section Establishing the data connec-
tion).
2
Under HEATER 2, select "SG Ready heat pump" for Consumer.
3
Select "Feed-in" under Starting threshold and enter the desired output in
watts at which the heat pump is to be switched on.
4
Under Switch-off threshold, select "Consume" or "Feed-in" and enter the
desired output in watts at which the heat pump is to be switched off.
Example 1: If you have selected "Consume" under the switch-off threshold and a
power of 500 W has been entered, the heat pump will be switched off as soon as
the power being drawn from the grid exceeds 500 W.
Example 2: If you have selected "Feed-in" under the switch-off threshold and
entered a power of 500 W, the heat pump will be switched off as soon as the
power being fed in is less than 500 W.
NOTE!
The heat pump must be connected to the same utility meter.
Between the switch-on and switch-off thresholds, the self-consumption of the
heat pump must also be taken into consideration. For example, if the heat pump
consumes 3000 Watts of electricity and a hysteresis of 500 Watts must be taken
into account, the switch-on threshold can be set to a feed-in of 3000 Watts and
the switch-off threshold to a consumption of 500 Watts.