9-50
P99 Motor Selection
Selects the motor to be used.
Data for P99 To use:
0 Fuji standard motors (8-series)
1 GE motors
3 Fuji standard motors (6- series)
4 Other motors
In order to perform automatic control features such as the auto torque boost/auto energy saving
and slip compensation or electronic thermal overload protection for the motor, the inverter
invokes the rated values and properties of the motor. To match the drive properties between the
inverter and motor, set the motor properties to this code and set function code H03 (Initialize
data) to 2 to initialize the motor parameter. This action automatically updates the data of
function codes P03 and P09 and the constants used inside the inverter.
When using a Fuji standard motor, select the data listed below according to the model.
- P99 = 0 for Fuji standard 8-series motors (current models)
- P99 = 3 for Fuji standard 6-series motors (conventional models)
For motors from other manufacturers or unknown models, set P99 to 4 (Other motors).
• If P99 is set to 4 (Other motors), the parameters of the Fuji standard 8-series
motor will apply as an alternative.
• The inverter also supports motors rated by HP (horse power: typical in North
America, P99 = 1).