3.2 Running Mode
3-7
Chap. 3 OPERATION USING THE KEYPAD
3.2.4 Jog (inch) the motor
In Running mode, pressing + keys at the same time (simultaneous keying) can make the inverter
ready for jogging. The
JoG
appears on the LED monitor.
To return the inverter from the ready-to-jog state to the usual running state, you need to press
+
keys simultaneously.
Using the external input signal command (JOG) also allows the transition between the ready-to-jog state
and usual running state.
Refer to function codes E01 to E03 in Chapter 9, Section 9.2.2 "E codes (Extension terminal
functions)" for details.
During jogging, the jogging frequency (C20) and acceleration/deceleration time for jogging (H54) will
apply. They are exclusively prepared for jogging and required to be set up individually.
When jogging the motor from the keypad, the inverter will only run while the
key is held down, and
contrarily the moment the key is released, the inverter will decelerate and stop the motor.
The transition ( + keys) between the ready-to-jog state and usual running state is
enabled only when the inverter is not in operation.