2.1.2 Installing Power Distribution Unit (2U)
This section explains how to install a 2U power distribution unit (12 outlet type or 16 outlet type) in a rack.
This section explains how to install a 12 outlet type power distribution unit as an example. This installa-
tion method can also be applied to a 16 outlet type power distribution unit.
1 Attach the M5 cage nuts to the rear rack pillar.
• Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power distribu-
tion unit base line.
1U
1U
2U
Power distribution unit
Power distribution unit
(Rack pillar: rear)
Power distribution unit
base line
M5 cage nut M5 cage nut
1st hole
3rd hole
4th hole
6th hole
1st hole
3rd hole
4th hole
6th hole
[Left] [Right]
• Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
Side view
M5 cage nut
Rack pillar (square hole)
Chapter 2
Rack Installation
2.1 Installing Power Distribution Unit (for Regions Other than EMEA&I)
30
FUJITSU Storage ETERNUS DX100 S3/DX200 S3 Disk storage system Configuration Guide (Basic)
Copyright 2014 FUJITSU LIMITED
P3AM-7652-02ENZ0