FHE-250 MANUAL 09 2014 ISSUE 2
Page 43
4
It is the law that any service work must be carried out by a Gas Safe Registered Engineer in the UK.
In IE service work must be carried out by a competent person.
SECTION 4 - MAINTENANCE
!
WARNING
Always turn off the gas supply at the gas service cock, and switch off and disconnect the electricity
supply to the appliance and any external controls before servicing or replacing components.
Maintenance on Gas appliances should only be carried out by competent, trained personnel who are
‘Gas Safe’ registered in the UK, and who have the necessary equipment to check combustion. If any
fault is found during these operations contact your Fulton representative.
Make the following checks for correct operation.
1. The correct operation of ANY secondary system controls should be proved. Operate each
control separately and check that the main burner or circulating pump, as the case may be,
responds.
2. Water circulation system;
a) With the system HOT examine all water connections for soundness.
b) With the system still HOT, turn off the gas, water and electricity supplies to the boiler and
drain down to complete the ushing process.
c) Rell and vent the system, clear all air locks and again check for water soundness.
d) Balance the system.
3. Check the condensate drain for leaks and check it is discharging correctly.
4. Finally set the controls to the Users requirements.
Note. If optional kits are tted then refer to the instructions supplied with the kits.
4.1
GENERAL
4.2
SAFETY
IMPORTANT NOTE: After completing the servicing or replacement of components always:
1. Test for gas soundness.
2. Test the burner manifold anges for soundness. This can be done with leak detection spray whilst
operating the boiler. The gas valve and controls must be shielded from the spray.
3. Check the water system is correctly lled and free of air. Air in the boiler could cause damage to
the heat exchanger. For this reason a non-isolatable automatic air vent is tted as standard on
all FHE boilers.
4. Check the module cover panels are correctly tted.
5. With the system hot examine all water connections for soundness.
CONTINUED...