ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
E99
Communication error between DSP and MAXSYS. Some MAXSYS boards are not
responding to DSP queries. There
might be a broken
communication cable, broken
power supply cable or fuse or
MAXSYS or DSP device has fatal
internal failure.
Cascade structure has been
changed, some DSP has lower
number of MAXSYS
connected.
Check cables and fuses related to affected MAXSYS
device. If unsuccessful, replace MAXSYS and/or DSP
board.
If cascade structure has been changed, re-do Auto
Detection.