EasyManuals Logo

G-Tek CR-2010 PRO Series User Manual

Default Icon
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
43
Specification
mA 50Ω Shunt External
CMRR
>100 dB@ 50, 60 Hz at 3 Sample per Second
NMRR
>50 dB@ 50, 60 Hz at 3 Samples per Second
Maximum Common Mode Voltage
5V AC
Isolation Channel EARTH
1.5KV 1 minute
Input Protection
30V AC/DC Max
Termination
Non-Interchangeable, Removable Plugs,
Individual for Each Input
Transmitter Power Supply
Non-Isolated 24VDC; 30Ma max, un protected
Environmental
Temperature
(Operation)5˚C to 45˚C / (Limiting) 0˚C to 50˚C
(Storage)-20˚C to 60˚C
Humidity
(Operation) 10 to 80 % RH Non-Condensing
(Storage) 5 to 90 % RH Non-Condensing
Altitude
<2000 meter
Power Requirement
Supply Voltage (Mains Operated)
85-264VAC 47-63Hz
Battery backup
Yes
DC Adapter Operated
Yes
Power
15W Max with Maximum Configuration
Fuse Type
None
Battery Backup*:
Battery
12V 7Ah External Lead Acid battery
Battery Charger
Yes
Battery Reverse Polarity
Protected
Minimum Back up
>12 Hrs.
Communication RS232/485*
Protocol
Proprietary
Baud Rate
4800
Parity
None

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the G-Tek CR-2010 PRO Series and is the answer not in the manual?

G-Tek CR-2010 PRO Series Specifications

General IconGeneral
BrandG-Tek
ModelCR-2010 PRO Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals