AN-53 Terminal 42 Output Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Holds the level of Output 42 if controlled by bus.
AN-54 Terminal 42 Output Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par. AN-50 Terminal 42 Output the output
will preset to this level.
3.8.7 AN-6# Analog Output X30/8
Parameters to configure the scaling and limits for Analog Output 1 associated with OPCGPIO General Purpose Field Installed Option Module.
AN-60 Terminal X30/8 Output
Option: Function:
Select the function of Terminal X30/8 as an analog current output. Depending on the selection the output
is either a 0-20 mA or 4-20 mA output. The current value can be read out in Keypad in par. DR-65 Analog
Output 42 [mA].
[0] * No operation When no signal on the analog output.
[100] Output frequency 0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[103] Motor Current Motor current 0 - 20 mA: Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160%
current) is equal to 20 mA.
[104] Torque rel to limit The torque setting is related to setting in par. F-40 Torque Limiter (Driving).
[105] Torq relate to rated The torque is related to the motor torque setting.
[106] Power Taken from par. P-07 Motor Power [kW].
[107] Speed Taken from par. F-53 Maximum Reference. 20 mA = value in par. F-53 Maximum Reference
[108] Torque Torque reference related to 160% torque.
[109] Max Out Freq In relation to par. F-03 Max Output Frequency 1.
[119] Torque % lim Torque % lim: Torque reference. par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[130] Output freq. 4-20mA 0 Hz = 4 mA, 100 Hz = 20 mA
AF-650 GP Programming Guide
105