[131] Reference 4-20mA par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback 4-20mA Feedback 4-20mA: par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
[133] Motor cur. 4-20mA Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160% current) is equal to 20 mA.
[134] Torq.% lim 4-20 mA The torque setting is related to setting in par. F-40 Torque Limiter (Driving).
[135] Torq.% nom 4-20 mA The torque setting is related to the motor torque setting.
[136] Power 4-20mA Taken from par. P-07 Motor Power [kW]
[137] Speed 4-20mA Taken from par. F-53 Maximum Reference. 20 mA = Value in par. F-53 Maximum Reference.
[138] Torque 4-20mA Torque reference related to 160% torque.
[139] Bus ctrl. 0-20 mA An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
[140] Bus ctrl. 4-20 mA An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
[141] Bus ctrl 0-20mA t.o. par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
[142] Bus ctrl 4-20mA t.o. par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
[149] Torque % lim 4-20mA Torque % Lim 4-20mA: Torque reference. par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20mA
par. F-50 Reference Range [-Max - Max] -100% = 4 mA; 0% = 12mA; +100% = 20mA
[150] Max Out Fr 4-20mA In relation to par. F-03 Max Output Frequency 1.
AN-61 Terminal X30/8 Min. Scale
Range: Function:
0.00 %* [0.00 - 200.00 %] Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum value as
a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the maximum output
value and 25% is programmed. The value can never be higher than the corresponding setting in par.
AN-62 Terminal X30/8 Max. Scale if value is below 100%.
This parameter is active when option module OPCGPIO General Purpose I/O Option Module is mounted
in the frequency converter.
AN-62 Terminal X30/8 Max. Scale
Range: Function:
100.00 %* [0.00 - 200.00 %] Scales the maximum output of the selected analog signal on terminal X30/8. Scale the value to the desired
maximum value of the current signal output. Scale the output to give a lower current than 20 mA at full
scale or 20 mA at an output below 100% of the maximum signal value. If 20 mA is the desired output
current at a value between 0 - 100% of the ful-scale output, program the percentage value in the pa-
rameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%),
calculate the percentage value as follows:
20
mA
/
desired
maximum
current
x
100 %
i
.
e
. 10
mA
:
20 4
10
x
100 = 160 %
AF-650 GP Programming Guide